INPUT VOLTAGE | 80 to 270 V AC |
SENSING VOLTAGE | 100 to 415 V AC |
OUTPUT EXCI. VOLTAGE | 100 V DC max. |
OUTPUT EXCI. CURRENT | 4 A DC. ( 12 A DC FOR 15 -SECONDS ) |
INPUT FREQUENCY | 50 / 60 Hz |
RESIDUAL BUILD UP | 5 V AC AT 50 Hz. |
VOLTAGE REGULATION | ±1 % |
UNDER FREQUENCY | FACTORY SETTING 47 Hz, REMOVE LINK FOR 57 Hz. INDICATION BY UFI - LED |
OVER EXCITATION CURRENT TRIP ( AMP / OEI ) |
25 SECONDS DELAY TIMER. ADJUSTABLE POT RANGE 0 - 4 ADC. INDICATION BY OEI - LED |
EXTERNAL POTENTIOMETER | ±5 % using 100 K Ohms pot |
DROOP ( Q1 & Q2, 5Amp C.T. ) | ±10 % at 5 Amperes |
TRIM ( A1 & A2 ) | ±5 V DC |
VIBRATION | 20-100Hz 50 mm/sec 100Hz - 2 Khz 3.3g |
OPERATING TEMPERATURE | -40 TO +70 C |
STORAGE TEMPERATURE | -55 TO +80 C |
RELATIVE HUMIDITY | 0 TO +70 C : 95 % |
FUSE ( FAST ACTING) | 4 AMPS ( Size: 20 X 5 mm) |
DIMENSIONS (L X B X H) | 150 X 115 X 38 mm |
WEIGHT | 415 gms |