Customization: | Available |
---|---|
Conditions of Use: |
Trailer Type, Marine, Land Use |
Usage: | Emergency Crew, Standby Unit, Common Units |
Still deciding? Get samples of US$ 50/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GAVR-12A | ||
Input | Sensing voltage | 180~260VAC,1 phase 2 wire |
Power voltage | 180~260VAC,1 phase 2 wire | |
Output | Voltage | Max. 90VDC@240VAC input |
Current | Continuous 4A | |
Current | Intermittent 7A for 10SEE | |
Resistance | Min.12Ω Max.100Ω | |
Voltage Build-up | Residualvolts at AVR teminal>5VAC | |
External Volts Adjustment | ±7% with 1KΩ 1 with trimmer | |
Soft start ramp time | 2sec. | |
Unit power dissipation | Max.8 Watt | |
EMI suppression | Internal electromagnetic interference filtering | |
Thermal. Drift | 0.03% per°C chage in AVR ambient | |
Under freqency protection | 60Hz system presets knee point at 55Hz | |
(Factory setting) | 50Hz system presets knee point at 45Hz | |
Volts regulation | <±1%(with 4% engine governing) | |
Environment | Vibration 3G@100~2K Hz | |
Operating temperature -40~60°C | ||
Relative humidity<95% | ||
Storage temperature -40~85°C | ||
Dimensions | 12.1*9.2*6cm |